Release Notes For InTouch Machine Edition

InTouch Machine Editionv7.1 + Service Pack 3 + Patch 4 (Thursday, December 18, 2014)

ID Type Description
4944 Change Request Implemented new Data protection feature to encrypt sensitive information
5188 Change Request Improved Trend Control to allow 'Cancel Window Zoom' if the user stops and re-runs during the runtime.
6612 Change Request Modified the Translation feature to no longer automatically import some of the Data from the Database configurations on screen control objects connected to Databases, such as Grid Control, Trend Control and Combo Box
7239 Change Request Modified the GetHardkeySN() function to properly return the updated value when removing or replacing the Hardkey after starting the application
4945 Requirement Modified the way the encrypted data is exchanged
7353 Requirement Enabled the ShowMessageBox function to work also when called by a Background Task
5954 Issue Resolved issue with a a buffer overflow being generated when reading a corrupted screen
6395 Issue Resolved issue with some parameters of the Trend Control object not working properly when using the Open() function and mnemonics
6493 Issue Resolved issue with using a String Tag on the Trend Control Duration field and zooming in, out and cancelling zoom not properly rounding the values
6506 Issue Resolved issue with GetAppPath() function returning a value with 2 backslashes at the end after the project has been downloaded to a Window PC target system
6613 Issue Resolved issue when using the Portuguese MUI and not being possible to see the correct number of tags on the text field on the lower right corner of the Development Environment that shows the tag count
6652 Issue Modified the Mobile Access to support iOS8
6655 Issue Resolved issue with PanelBuilder Import wizard creating an invalid scheduler worksheet when importing projects without a tag assigned to the screen number
6656 Issue Modified the mobile access to support screen name with space when specifying the screen name in the query string (e.g.: http://localhost/ma?screen=Screen%20With%20Space)
6773 Issue Enhanced the login page to display more precise information when the logon fails.
6803 Issue Fixed problem with functions GetTagValue and SetTagValue for Mobile Access. The functions were not working properly if the TimeStamp field was part of the tag name specified e.g.: GetTagValue( Tag->TimeStamp ).
6808 Issue Resolved issue with the Collaboration Tool not properly handling the Email information saved on the Alarm worksheets
6977 Issue Resolved issue with the Trend Control object where the Cursor Output Value, in certain situations, was displaying a wrong value when the screen having this object was first open
7038 Issue Resolved issue with the print orientation not working properly when printing using the trigger on the Grid Control object
7179 Issue Fixed system error on Mobile Access when loading several clients simultaneously.
7210 Issue Modified the dialogs of certain objects on the Web Thin Client to no longer have the “Close” system menu, no longer be able to drag them and do not allow right clicking on them
7221 Issue Resolved issue with the Mobile Access that, on certain situations, when saving screens, the font object was being set to an invalid value.
7238 Issue Resolved issue with the Date and Time functions not returning the correct values depending on the Daylight Saving status and parameters
7293 Issue Resolved issue with Secure Viewer connected to redundant servers having issues when switching servers
7374 Issue Modified the Mobile Access to display '????' in the tag value when an invalid tag or an invalid array index is specified. Prior to this change Mobile Access would display System.Object
7380 Issue Fixed an issue with Mobile Access VBScript parser where function calls receiving array tag(s) as parameter(s) would not work as expected.
7430 Issue Resolved issue with the Auto-LogOff feature not working properly when the Security System is configured to LDAP mode
7440 Issue Resolved issue with the SetLanguage function causing errors on the TCP/IP Server task when called simultaneously from different Thin Clients
7458 Issue Resolved issue with the modifier keys causing commands configured on the “On Up” action of the Command animation to be executed
7465 Issue Resolved issue with Remote Management not being able to connect to PocketPC in ActiveSync mode
7504 Issue Resolved issue with the Security System, when switching between LDAP and Local modes, and restarting the software, causing the LDAP settings not to be retained
7522 Issue Resolved issue errors that were happening when we tried to close certain screens that were already invalid
7646 Issue Resolved issue with the SNMP agent not working properly
7747 Issue Resolved issue with Secure Viewer not displaying Linked Pictures addressed with absolute paths
8132 Issue Modified the EmbeddedView run-time to remove the requirement of having the C++ libraries in the embedded device image

InTouch Machine Editionv7.1 + Service Pack 3 + Patch 3 + Hotfix 2 (Wednesday, November 12, 2014)

ID Type Description
7458 Issue Resolved issue with the command animation, that when pressing and releasing one of the modifier keys (i.e. Ctrl, Alt, Shift), during the Runtime, could cause the commands configured on the “On Up” action to be executed even if they were not associated to keyboard shortcuts.

InTouch Machine Editionv7.1 + Service Pack 3 + Patch 3 (Tuesday, October 28, 2014)

ID Type Description
3696 Requirement Implemented Tag Integration interface for the AutomationDirect DoMore PLC Family.
5394 Requirement Enhanced the Mobile Access solution to support the Security System Auto LogOff feature
5859 Requirement Added support for General alarm fields for the TagsDBSetAlarm and TagsDBGetAlarm functions
5998 Requirement Implemented capability to customize the Viewer icon on the Task Bar.
6061 Requirement Created a new built-in function, GetLastESignUser(), that returns the name of the user authenticated to execute a screen Command (animation) with E-signature
6262 Requirement COSYS Tag Integration: added ARTI3 support
4713 Issue Resolved issue with the translation feature not working on the Combo Box object when using data source as Database
4726 Issue Changed the way Development Environment handles the Fill Effects for rectangles when the system is targeted for an Embedded runtime
5032 Issue Resolved issue with the Import Wizard Tags Filter Dialog not working for any language other than English
5166 Issue Resolved issue with Remote Management, when connectign to a EmbeddedView system, if your target folder is not a Subfolder of the Remote Agent (CEServer), the selected target folder is not kept
5299 Issue Resolved issue with the Text Data Link dynamic property not being updated when the Screen Attribute parameter Hide screen instead of closing it was checked
5330 Issue Resolved an issue where an incorrect message was displayed when the project developer tried to insert the same System Symbol more than once.
5376 Issue Resolved issue with the Ctrl+F Find functionality ignoring the last row on any worksheet on the development environment, such as Driver, Scheduler, Math, and so forth
5616 Issue Modified the Protection Manager to allow you to select a MAC address when you change your softkey license. This is necessary because the license's site code is based on the computer's MAC address, and the computer may have more than one MAC address if it is connected to a VPN or otherwise using a virtual NIC at the time that you change your license.
5652 Issue Fixed a problem with the OPC DA 2.05 worksheet where the Div column would display a wrong label.
5666 Issue Resolved issue with the popup input for text object not being properly displayed when more than one monitor was being used
5804 Issue Resolved issue with Remote Management experiencing timeout problems when downloading projects to remote computers when the Remote Agent is configured with users and passwords on its Security System
5871 Issue Resolved issue with the Trend Control object when enabling the Advanced-> Auto Save option, it would cause some tags configured in the fields to not work properly
5884 Issue Resolved an issue where the built-in function TagsDBAddTag would not accept new tag names beginning with the "@" character.
5910 Issue Modified the OPC XML/DA to properly set the quality of the tags to BAD when the client fails to connect to the server.
5939 Issue Resolved issue with the Output Window and LogWin module no longer showing Database messages that would include important information such as wrong table or column names when using the Grid Control
5946 Issue Resolved issue with the Trend Control object not accepting mnemonics on the Axes->Duration field
5976 Issue Resolved issue where opening the “Config” window of the Command property Object Properties, and clicking on the “Cancel” button, would delete the VBScript configured on it
5978 Issue Resolved issue with Alarm Control not being able to properly use the Filter Expression when it had Custom fields containing lower case characters or when the last Custom field was being used
5987 Issue When deleting a screen using the Project Explorer treeview, now all the files related to that screen that were saved on the Project’s Web folder, such as the html, scc and ssma files are also deleted
5997 Issue Resolved issue with the Report task not working properly when some Asian characters were used
5999 Issue Resolved issue with the capability to save the alarm state whem the alarm is generated by the Driver and/or OPC, the alarm selected tag showed a string in the format #:#:#:# instead of the tag name.
6009 Issue Resolved issue with the tag not having its value properly displayed on some specific screen objects with animations.
6059 Issue Modified the built-in RunGlobalProcedureOnTrigger() function to work also when called from a Secure Viewer Thin Client
6060 Issue Resolved issue with the Security System when using Tags in the “Password Aging” and/or in the “E-signature timeout” fields from “Security System > Groups > [GroupName] > Advanced” dialog being reset to their “lowest value after running the application” when executing GetUserFullName()
6095 Issue Resolved issue with the Remote Management tool not allowing the user to select a non-empty folder as your target application when browsing for a target folder in the development environment
6107 Issue Modified the Database Functions to display an error message on the log when the maximum number of connections with the database is exceeded.
6140 Issue Resolved issue with the Virtual Keyboard not being properly placed when the user had more than one monitor
6167 Issue Resolved issue where it was not possible to configure mnemonics on the Trend Control > Axes > Duration field, even though we could configure a tag on the same field
6185 Issue Resolved issue with using the Print button on the Trend Control object was not printing values on the SPC columns when they are configured to be displayed (Min, Max, Avg, etc...)
6314 Issue Resolved issue with key combinations on the Command animation not working on the OnUp scripts when one of the keys was being released first
6325 Issue Modified the Mobile Access scripting engine to properly handle line breaks and user functions with suffix MsgBox.
6432 Issue Resolved issue with the X-Ref tool wrongly showing that the tags would be present in certain documents where they were not
6453 Issue Resolved issue with the Trend Control using Data Source as Text and the X-Axis containing Date/Time information
6522 Issue Resolved issue with the Mobile Access interface where the Mobile Access Client would stop receiving tag changes from the server.
6582 Issue Modified the Mobile Access to prevent fatal error when closing a screen with Combo Box before the Combo Box can load its data.
6792 Issue Resolved issue with security system in distributed mode causing the TCP/IP server task to create unnecessary connections.
7458 Issue Resolved issue with the command animation, that when pressing and releasing one of the modifier keys (i.e. Ctrl, Alt, Shift), during the Runtime, could cause the commands configured on the “On Up” action to be executed even if they were not associated to keyboard shortcuts.

InTouch Machine Editionv7.1 + Service Pack 3 + Patch 2 (Friday, August 08, 2014)

ID Type Description
2872 Requirement Modified the Trend task to make it easier to troubleshoot when historical data are not saved correctly.
3316 Change Request Modified the message that is displayed when the project developer clicks "Trust server certificate" in the security settings for an OPC UA connection (OPC UA > Connections > Server Configuration > Security), in order to warn them when the certificate is self-signed.
4994 Change Request Implemented the new built-in functions TranslationLookupLoad, TranslationLookupGet, and TranslationLookupClose, which allow the project developer to create lookup maps between different languages. For more information, see the documentation.
4995 Change Request Improved the ADO.NET database gateway (StADOSvr) to make it possible to specify a locale (i.e., language and country) for database queries, rather than use the locale that is specified in the host's system settings.
5685 Change Request Modified the built-in function CheckESign to take a security access level as an optional parameter. Previously, the function would validate against level 0, and level 0 is still the default, but this parameter allows the project developer to specify any level.
3989 Issue Resolved an issue with Linked Symbols that are configured to use Class tags imported via tag integration.
4025 Issue Resolved an issue with the built-in function FileWrite, where it did not properly handle the Visual Basic CRLF character (vbCrLf).
4372 Issue Modified the built-in function SetViewerPos to be able to take negative values as parameters. This is to make it easier to manage the Viewer on multiple monitors.
4461 Issue Resolved an issue with the Smart Message object not displaying the last configured message.
4545 Issue Modified the interface between the development station and the target station in order to avoid errors when using the "Get From Target" command (Remote Management > Import) to import projects from the target station.
4903 Issue Resolved issues with Runtime for Windows Embedded Compact not properly interacting with SQL CE 3.5.
5059 Issue Resolved an issue with the project security system where, if a project had been running for extended period (i.e., more than one week), creating a new user would generate errors.
5064 Issue Resolved an issue where the OPC UA Client task would sometimes crash if it attempted a read/write operation while it was disconnected from the OPC UA server.
5092 Issue Modified the ADO.NET database gateway (StADOSvr) to work even if Microsoft .NET Framework 4 is not installed on the computer that hosts the gateway. .NET Framework 4 became a requirement when support for Wonderware Historian was implemented in a previous release (see item 3423). This modification ensures that the gateway will continue to work for most database connections, but if you plan to connect to a Historian database, .NET Framework 4 is still required. For more information, see the documentation.
5099 Issue Resolved an issue with the EmbeddedView runtime where it did not show the window menus (File, Security, Tools) even if it was configured to do so (Project Settings > Viewer).
5185 Issue Resolved an issue where the "Test Screen" command would change the background color of Text objects that have the Text Data Link animation applied to them. (To access the "Test screen" command, right-click in the project screen editor.) See also item 5186.
5186 Issue Resolved an issue where the "Test Screen" command would change the size of some screen objects that have the Position/Visibility animation applied to them. (To access the "Test screen" command, right-click in the project screen editor.) See also item 5185.
5208 Issue Modified the OPC UA Client and OPC XML/DA Client tasks to set tag quality to BAD when the connection to the OPC Server is lost.
5210 Issue Resolved an issue where the project security system did not verify that a client request had been processed before the next request was sent. This sometimes caused the project to become unstable, when the client received responses to requests that had timed out.
5247 Issue Modified both the History-to-Text utility (HST2TXT.exe) and the built-in function Hst2Txt to improve their handling of Daylight Saving Time (DST).
5292 Issue Resolved an issue that was causing project file tagl.txt to be deleted under certain circumstances.
5313 Issue Resolved an issue with the "Built-in Dialogs Scale" setting (Project Settings > Web) where if it was set to anything other than 100%, it caused the "User Name" combo box in the "Log On" dialog box to be displayed incorrectly.
5330 Issue Resolved an issue where an incorrect message was displayed when the project developer tried to insert the same System Symbol more than once.
5351 Issue Resolved an issue where the built-in function GetOS would return incorrect values when called on Windows Embedded Standard.
5377 Issue Resolved an issue with the built-in functions PrintWindow and SaveScreenshot where, if the functions were used to print or save a closed screen that contained a Trend Control object, the object was not printed or saved correctly.
5378 Issue Resolved an issue where the run-time user could accidentally close the viewer on Windows Embedded if they clicked or tapped the top-right corner of the project screen.
5392 Issue Resolved an issue where a screen file sometimes became corrupted if the project developer deleted an ActiveX control from the screen and then saved it.
5455 Issue Resolved an issue with the Grid Control object where if it was configured to use Class Tag as its data source, it would show BAD quality for the wrong array elements.
5616 Issue Modified the Protection Manager to allow you to select a MAC address when you change your softkey license. This is necessary because the license's site code is based on the computer's MAC address, and the computer may have more than one MAC address if it is connected to a VPN or otherwise using a virtual NIC at the time that you change your license.
5634 Issue Implemented safeguards to prevent memory overflow errors that sometimes occurred when using TreeView Control (TreeView.ocx) in a project screen.
5804 Issue Resolved issue with Remote Management experiencing timeout problems when downloading projects to remote computers when the Remote Agent is configured with users and passwords on its Security System
5884 Issue Resolved an issue where the built-in function TagsDBAddTag would not accept new tag names beginning with the "@" character.

InTouch Machine Editionv7.1 + Service Pack 3 + Patch 1 (Friday, July 04, 2014)

ID Type Description
4864 Change Request Enhanced Studio Mobile Access (SMA) messages to precisely indicate when compression is enabled (unsupported) or when the screen is not published. Also added instructions to the error message explaining how to open the browser console to get additional information.
3649 Issue Modified the Studio Mobile Access (SMA) Thin Client interface to support connection to the server through routers.
3929 Issue Modified the Alarm/Event Control object to sort messages properly by Date/Time, even when the historical data is saved in an external database.
4349 Issue Modified the label ""Extern Translation"" to ""Enable Translation"" on the ""Object Properties > Messages"" dialog of the Smart Message object (on the development environment) for consistency.
4374 Issue Resolved issue with a form being displayed by the Studio Service Tray in some systems
4386 Issue Modified the graphic interface to support data entry for objects with mnemonics even when the ""Use popup input for text objects"" option from Project >> Settings >> Viewer is enabled (checked).
4426 Issue Modified the Driver task to support writing floating point (real) values with precision beyond the 6th decimal digit for drivers that handle real values as string
4509 Issue Resolved issue with the Text Object alignment of text being ignored when using the translation tool to switch to a different language during the runtime
4557 Issue Modified the Collaboration Server to make sure that the tags database main file (Tagl.txt) is converted to XML format when applicable, in order to avoid errors.
4585 Issue Modified the Tag Integration for the ""AutomationDirect Koyo"" provider to support CSV files with ""unassigned items"".
4680 Issue Modified the OPC DA/XML task to recognize the data type of items that were not ""available"" for the OPC Server when the OPC DA/XML Client task was launched, but eventually become ""available"" (e.g.: connect the device to the network only after the OPC DA/XML task was launched). The new algorithm allows the OPC DA/XML Client to recognize the data type of items that become available during the runtime and, consequently, be able to write values to such items.
4681 Issue Improved the performance of the Tag Integration for the ""RSLogix 5000 family"" provider when loading tag names from the L5K file. Moreover, the Tag Integration was modified to ignore ""Encoded Data blocks"" while importing the remaining tags available in the L5K file.
4728 Issue Modified the Trend Task to avoid missing samples when the format of the Trend worksheet(s) was set to Proprietary (*.hst files).
4752 Issue Modified the OPC XML/DA Client task to indicate bad quality for the tag(s), if any, associated with a blank or invalid item, while communicating properly with the remaining items properly configured in the same OPC XML/DA Client worksheet.
4753 Issue Modified the OPC XML/DA Client task to recognize changes implemented in the OPC XML/DA Client worksheets and saved while the task was running - online configuration.
4766 Issue Modified the TCP/IP Server to handle legacy alarm controls asynchronously, preventing possible system errors
4770 Issue Modified the Collaboration server to prevent it from displaying error messages when editing tags in a project without any classes (Project Explorer > Global > Classes).
4843 Issue Modified the ImportXML built-in function to handle the size (height and width) of polygons properly and avoid settings unexpected values for the object width when editing it with the development environment (screen editor) after importing the screen(s).
4890 Issue Resolved issue with the tag quality remaining Uncertain after the user attempted to enter values out of the configured min and max range
4942 Issue Resolved an issue with the alignment of Text objects in the screen worksheet, when the Text Data Link animation was applied to the objects and the Auto Size option was enabled.
5081 Issue Corrected the Studio Mobile Access log system that was reporting a wrong line number when a script had a VBScript code line break (""_"" character) inside a VBScript comment.
5101 Issue Modified the Trend Control to display the pens in Online Mode, even if the values are saved in an external database with TimeStamp set to Local Time (not UTC).
5116 Issue Resolved issue with disabling all objects that can receive focus in a screen during the runtime could cause unstable behaviors
5181 Issue Update OPC OpenSSL to the latest version to address CCIRC Advisory AV14-031 OpenSSL vulnerability
5184 Issue Modified the Trend/Alarm database interface to prevent 100% CPU usage when inserting data on relational databases
5197 Issue Modified the asynchronous database insertion algorithms to prevent instability that could cause system errors
5213 Issue Improved the Studio Mobile Access (SMA) script error information to allow better identification of the script that is preventing the screen from opening.
5215 Issue Improved the Studio Mobile Access to support the VBScript code ""If $Tag Then $Function() Else $Function() End If"" all in the same line.

InTouch Machine Editionv7.1 + Service Pack 3 + Patch 4 - Known Issues (Thursday, December 18, 2014)

ID Type Description
871 Issue Resize Dynamic Property not working properly on Open Polygons [WORKAROUND]: If you need to use resize try using other shapes or pictures
1634 Issue Right-click does not work correctly when objects are grouped and "Execute only topmost object commands" is enabled [WORKAROUND]: Ungroup the objects
1748 Issue Import Wizard does not import Opc Ua, Opc Xi and Tag Integration configuration files [WORKAROUND]: Copy the Opc Ua, Opc Xi, and Tag Integration settings manually from the source project.
2033 Issue CEServer for EmbeddedView v7.0 does not properly handle when there is a MAC ID in the Registry [WORKAROUND]: The workaround is to manually clear the following registry key: This is the Registry Key: SYSTEM\\CurrentControlSet\\Control\\Class\\{4D36E972-E325-11CE-BFC1-08002bE10318}
2134 Issue Validation of the Custom Resolution fields happen when creating new projects even if you have selected one of the pre-defined resolutions [WORKAROUND]: Change the resolution back to Custom and write a value between 240 and 10000 on both fields. Then, choose one of the pre-defined resolutions on the Combo box
2501 Issue Linked pictures do not work on the Windows Embeeded runtime [WORKAROUND]: Add the files im31*.* and the file imgman32.dll to the product BIN folder.
2526 Issue Combo-Box connected to Database does not work well if the screen has the option "Hide screen instead of closing it" checked [WORKAROUND]: Load the database information on an array tag and place the array tag on the Combo-Box
2534 Issue The Mobile Access legend is not properly redrawn on some specific conditions [WORKAROUND]: Toggle the cursor to for the legend redraw
3733 Issue Ack alarms when double clicking on the Extra Columns "Custom Fields" in the alarm object does not work. [WORKAROUND]: Enable other column than "Custom Fields" and use it for ack the alarm.
4821 Issue If you modify a tag field that applies to the entire array Mobile Access will not synchronize the value to all the array elements [WORKAROUND]: Because the field has the same value for all indexes, you should use one index for all the locations where you need the field.